1. Overview
The HK-SG-200 Audible and Visual Alarm is designed to alert on-site personnel in the event of a fire or other emergency. It can be installed directly on combustible gas detectors as a local alarm unit or mounted on explosion-proof instruments in hazardous industrial areas. When the connected device enters an alarm state, the HK-SG-200 emits strong sound and light signals to warn personnel.
This alarm complies with the explosion-proof standards GB 3836.1-2010 “Explosive Atmospheres – Part 1: Equipment – General Requirements” and GB 3836.2-2010 “Explosive Atmospheres – Part 2: Equipment Protection by Flameproof Enclosure ‘d’.”
2. Technical Specifications
-
Operating Voltage: 24VDC
-
Flashing Frequency: 1 flash/second
-
Sound Pressure Level: 85 dB
-
Alarm Output: Audible + Visual
-
Electrical Interface: M20 × 1.5
-
Ingress Protection: IP66
-
Explosion-Proof Grade: Ex d IIC T6 Gb / Ex tD A21 IP66 T80°C
-
Operating Temperature: -40℃ to +60℃
-
Operating Humidity: ≤93% RH
-
Power Consumption: <2W
-
Dimensions: Φ36 × 98mm × 67mm
-
Weight: 340g
3. Basic Function
When the alarm receives a triggering signal from a connected detector, it outputs a strong audible and visual alert to notify personnel.
4. Structural Features
The HK-SG-200 features a compact and simple structure for convenient installation. Key components include:
-
Alarm light
-
Casing
-
Buzzer
-
24V power wires (Red = Positive, Black = Negative)
(Refer to included diagram for dimensions and layout.)
5. Installation Notes & Explosion-Proof Requirements
-
Wiring
The alarm must be connected with correct polarity: red wire to positive (+) and black wire to negative (–). Incorrect wiring may damage internal electronic components. -
Precautions
-
Periodically inspect and maintain the high-temperature sealing material at cable entry points. Replace if aged or damaged.
-
Do not arbitrarily replace or alter components or parts that affect the explosion-proof integrity.
-
Always disconnect power before performing any maintenance; live operation is strictly prohibited.
-
Avoid impacts or strong shocks during use.
-
Alarms in explosive environments must be calibrated once per year.
-
Alarms operating under high temperature, corrosive, or vibratory conditions should be calibrated every six months.
-
Any product that has passed explosion-proof testing must not be modified or tampered with.
-
6. Warranty Policy
This product has undergone aging, calibration, and full inspection per national standards.
Warranty Term: 1 year from purchase date, covering free repairs or replacement.
Exclusions:
-
Damage from force majeure, misuse, improper installation, or human error
-
Unauthorized disassembly or modification
-
Damage during shipping
-
Damage due to dropping or impact
7. Contact Information
Sales Hotline: +86 21-68901087
Technical Support: +86 21-68910600
Fax: +86 21-33275717
Address: Floor 2, Building 27, No. 58, Lane 7224, Hunan Highway, Pudong, Shanghai
Email: pudongleyun888@126.com





Reviews
There are no reviews yet.