HK2000 Gas Alarm Controller

Compare

HK2000 Series

Combustible Gas Alarm Controller

Installation and Operation Manual


1. Product Overview

The HK2000 Combustible Gas Alarm Controller is designed for industrial environments. It works with our 4-20mA current-output gas detectors to form a gas alarm control system. When combustible gas or liquid vapors are detected in the monitored area, the detector transmits a 4-20mA current signal proportional to the gas concentration to the controller. The controller processes the signal, displays the gas concentration, and triggers audible/visual alarms and control signals if the concentration exceeds preset thresholds (low/high limits). This enables graded control to prevent accidents.

The HK2000 controller includes ​3 relays​ for low-limit alarms, high-limit alarms, and faults.

Key Features

  • High-brightness LED display for real-time gas concentration monitoring and menu interaction.
  • Compliant with Chinese National Standard ​GB16808-2008​ for combustible gas alarm controllers.

Technical Specifications

Parameter Description
Compliance GB16808-2008
Main Power 220V AC, 50Hz
Backup Power 2×12V DC 1.3Ah lead-acid batteries
Power Consumption ≤2W
Detector Interface 4-20mA
System Capacity 1 detector per loop
Display High-brightness LED
Status Indicators LED indicators
Alarm Levels Low-limit (1st level), High-limit (2nd level)
Audible Alerts Fault tone, Alarm tone
Event Logging 1,000 alarm records, 200 fault records
Relay Outputs 3 relays
Relay Rating 3A @ 24V DC / 3A @ 250V AC
Communication RS485 (Modbus RTU protocol)
Mounting Wall-mounted
Operating Temperature 0°C to 40°C
Operating Humidity ≤95% RH (non-condensing)

2. Installation and Wiring

2.1 Mounting

The HK2000 controller is wall-mounted. Drill two 10mm-diameter holes (depth: 40mm) at marked positions on the enclosure. Secure the unit to the wall using M6 expansion bolts.

2.2 Dimensions

(Note: Include dimensional drawings here if available.)

2.3 System Configuration

The HK2000 controller connects to detectors as shown in the system diagram.

2.4 Terminal Definitions

Terminal Description Terminal Description
L Live wire N Neutral wire
PE Ground wire PE Ground wire
BAT+ Backup power (+) BAT+ Backup power (+)
BAT- Backup power (-) BAT- Backup power (-)
A RS485 (+) A RS485 (+)
B RS485 (-) B RS485 (-)
lout 4-20mA output lin 4-20mA input
LR+ Low-limit relay (+) DT+ Detector power (+)
LR- Low-limit relay (-) DT- Detector power (-)
HR+ High-limit relay (+) FR+ Fault relay (+)
HR- High-limit relay (-) FR- Fault relay (-)

3. Operation Guide

3.1 Display and Indicators

LED Indicators

  • Alarm: Lights when any detector triggers an alarm.
  • Fault: Lights when a detector or system fault occurs.
  • Main Power: Active during AC220V operation.
  • Backup Power: Active during battery operation.
  • Mute: Lights when alarms/faults are silenced.

Keypad Functions

  • Confirm: Accept inputs.
  • Exit: Return to previous menu.
  • Reset: Clear faults/alarms and restore defaults.
  • Self-Test: Test audible/visual alerts.
  • Query: Access event logs.
  • Settings: Enter configuration menu (password required).
  • Mute: Silence alarms/faults (new alarms reactivate sound).
  • Arrow Keys: Navigate menus.

3.2 Operational States

Normal Monitoring

LED displays real-time gas concentration.

Alarm States

  • Low-Limit Alarm: Gas concentration ≥ low threshold. Triggers audible/visual alerts and closes low-limit relay.
  • High-Limit Alarm: Gas concentration ≥ high threshold. Triggers louder alarms and closes high-limit relay.

Fault State

Detector/system faults trigger fault indicators, audible alerts, and close the fault relay. Alarms auto-clear when faults resolve.

Note:

  • Press ​Mute​ to silence alarms temporarily.
  • Press ​Reset​ to clear alarms after gas concentration drops below thresholds.

3.3 System Menu

Access Levels

  • Normal Access: View logs and mute alarms (no password).
  • Level 1 Access: Reset or self-test (default password: Left/Left/Left/Left for reset; Right/Right/Right/Right for self-test).
  • Level 2 Access: Configure parameters (default password: Up/Down/Left/Right).

Configuration Menu

Parameter Description Access Level Notes
rtc Real-time clock Level 2
rANG Detector gas range Level 2
A1 Low-limit threshold Level 2
A2 High-limit threshold Level 2
Addr RS485 address Level 2
nodE RS485 mode Level 2 0=CRT, 1=Modbus RTU
bAt Backup power enable Level 2 0=Disable, 1=Enable
CALI Calibrate 4-20mA input Level 2
CALO Calibrate 4-20mA output Level 2

4. Packaging, Transport, and Storage

  • Packaged in foam-lined cartons.
  • Suitable for rail, road, or air transport. Avoid impacts to the top surface.

5. Safety Guidelines

  • Do not modify internal components. Unauthorized adjustments may void warranties.
  • Ensure proper grounding for lightning protection and EMC compliance.
  • Secure all cables with waterproof connectors.
  • Keep enclosure door locked during operation.

Shanghai Huikong Electronic Technology Co., Ltd.​
Address: 2nd Floor, Building 27, No.58, Lane 7224, Hunnan Highway, Pudong New District, Shanghai
Tel: +86-21-68901087
Fax: +86-21-33275717

Reviews

There are no reviews yet.

Be the first to review “HK2000 Gas Alarm Controller”

Your email address will not be published. Required fields are marked *