JTW-LD-KC82001 cable-type wire-type temperature-sensitive fire detector (hereinafter referred to as the detector) is a kind of irrecoverable cable-type wire-type temperature-sensitive fire detector products, the detector to the People’s Republic of China national standard GB16280-2014 “wire-type temperature-sensitive fire detector” as its main design basis, with a fixed-temperature fire detection and alarm characteristics. The detector consists of temperature-sensitive cable, signal processing unit and terminal unit, and adopts relay passive contact output, which can be conveniently used with fire alarm controllers of different manufacturers, and is widely used in the early detection of fire in metallurgy, electric power, petrochemical and other industrial occasions.

Compare

Installation and Operation Manual for JTW-LD-KC82001/85 & JTW-LD-KC82001/105 Cable-Type Linear Heat Detectors


1. Overview

The JTW-LD-KC82001/85 and JTW-LD-KC82001/105 Cable-Type Linear Heat Detectors (hereinafter referred to as “the Detector”) are non-resettable fire detection products. Designed in compliance with the Chinese National Standard GB16280-2014 Linear Heat Detectors, they provide fixed-temperature fire detection and alarm functionality. The system consists of a sensing cable, a signal processing unit, and a terminal unit. It utilizes relay-based dry contact outputs for seamless integration with fire alarm control panels from various manufacturers. These detectors are widely used in industrial environments such as metallurgy, power, and petrochemical facilities for early-stage fire detection.


2. Working Principle

The linear heat detection system comprises three components: the sensing cable, signal processing unit, and terminal unit. The sensing cable employs a three-core structure:

  • Conductor ①​ (coated with thermosensitive material),
  • Conductor ②,
  • A multi-strand metallic wire.

Conductor ①​ and the multi-strand metallic wire are wrapped in aluminum foil. The resistance between them varies with ambient temperature. ​Conductor ②​ and the multi-strand metallic wire maintain stable resistance below the non-activation temperature. However, resistance drops irreversibly when ambient temperature reaches or exceeds the alarm threshold.

The signal processing unit monitors the sensing cable continuously via internal circuits (signal acquisition, amplification/conversion, and display circuits). It triggers alarms for abnormal temperature rises, cable breaks, or short circuits.


3. Features

  1. Complies with GB16280-2014 Linear Heat Detectors (1-meter heated length for activation).
  2. Fixed-temperature alarm thresholds: ​85°C​ or ​105°C.
  3. Maximum cable length: ​​≤200 meters.
  4. Independent dry contact outputs for ​fire alarm​ and ​fault alarm.
  5. Detects open/short circuits in the sensing cable.
  6. Twisted cable structure ensures mechanical durability and EMI resistance.

4. Technical Specifications

  1. Alarm Temperature: 85°C ±10% / 105°C ±10%
  2. Operating Ambient Temp.​: -40°C ~ 50°C / -40°C ~ 70°C
  3. Humidity: ≤95% RH (non-condensing)
  4. Power Supply: DC24V (9V–30V range)
  5. Standby Current:
    • ≤25mA @30V, ≤40mA @24V, ≤90mA @10V
  6. Alarm Current:
    • ≤40mA @30V, ≤70mA @24V, ≤160mA @12V
  7. Self-Resetting Fuse: 300mA
  8. Outputs:
    • Fire Alarm: Relay (closed on alarm)
    • Fault Alarm: Relay (changeover contacts)
  9. Relay Rating: 1A/24VDC
  10. Dimensions:
    • Signal Processing Unit: 160×120×57mm
    • Terminal Unit: 80×82×56mm

5. Wiring Configuration

5.1 Sensing Cable Core Structure

5.2 Signal Processing Unit & Terminal Unit

5.3 Signal Processing Unit Terminals

  • Terminals 1–4: DC24V power input (1/2: +24V; 3/4: GND).
  • Terminals 5–6: Fire alarm relay output (closed on alarm).
  • Terminals 7–9: Fault relay output (7–8: NC; 7–9: NO).
  • Terminals 10–12: Sensing cable connections:
    • Terminal 10: Conductor ②
    • Terminal 11: Multi-strand metallic wire
    • Terminal 12: Conductor ①

    Note: Remove aluminum foil before wiring. Do NOT connect foil to terminals.

5.4 Terminal Unit Terminals

  • Terminal D: Conductor ①
  • Terminal C: Multi-strand metallic wire
  • Terminal B: Conductor ②

    Note: Remove aluminum foil before wiring.

5.5 Signal Processing Unit Buttons

  • ​”Fault Test”​: Simulates short-circuit fault.
  • ​”Fire Reset”​: Resets fire alarm test.

5.6 Integration with Fire Alarm Systems

Connect the detector’s alarm outputs to the fire alarm control panel via I/O modules.


6. Applications

  1. Cable tunnels, cable corridors, cable mezzanines.
  2. Conveyor belts or systems.
  3. Hydraulic stations, oil pipelines, lubricant storage.
  4. Power distribution systems (transformers, substations, MCCs).
  5. Warehouses, storage racks.
  6. Industrial processes and material handling.
  7. Chemical storage facilities.
  8. Cleanrooms, electrical control rooms, server rooms.

7. LED Indicators (Signal Processing Unit)​

  1. Green (Run)​: Blinking = Normal operation.
  2. Yellow (Fault)​:
    • Blinking = Open circuit or short between conductors.
    • Steady = Short between conductor and metallic wire.
  3. Red (Fire)​: Steady = Temperature exceeds alarm threshold.

8. Installation Guidelines

8.1 Sensing Cable Installation

  • Ensure ​insulation resistance >20MΩ​ between power terminals (D+/D-) and ground.
  • Install in a continuous, tap-free, branch-free layout. Use ​dedicated junction boxes​ for splices.
  • Preferred methods: Linear, spiral, or sinusoidal routing. Maximize contact with protected surfaces using clamps.
  • Avoid sharp bends (minimum radius ​**>0.2m**), impacts, or compression.
  • Post-installation: Verify insulation integrity and waterproofing.
  • Prohibited: Use in environments exceeding ​50°C/70°C​ or on surfaces >50°C/70°C.

8.2 Signal Processing Unit & Terminal Unit

  • Mount indoors at ​1.5m height​ on walls/frames. For outdoor use, install in weatherproof enclosures.
  • Ensure sealing to maintain IP rating and prevent false alarms.

8.3 Post-Installation Test

Perform a fire alarm simulation using the ​​”Fire Test”​​ button.


9. Troubleshooting

  1. Check LED indicators for fault type.
  2. Use ​dedicated junction boxes​ for cable splices.
  3. For intermittent alarms:
    • Inspect sealing of units and junction boxes.
    • Check for cable damage.
    • Verify terminal connections.
  4. Contact manufacturer if unresolved.

Shanghai Huikong Electronics Technology Co., Ltd.​
Address: 2F, Bldg. 27, No.58, Lane 7224, Hunan Road, Pudong, Shanghai, China
Tel: +86-21-68901087 Fax: +86-21-33275717
Website: http://www.shhkdz.com

Reviews

There are no reviews yet.

Be the first to review “JTW-LD-HK82001/85”

Your email address will not be published. Required fields are marked *